A 5 A CT secondary circuit with 200 ft of #10 AWG wire and a single relay can easily exceed 10 VA burden — enough to push a C100 CT into saturation, causing relay misoperation or meter errors that go unnoticed until a fault occurs. Getting burden rig...
Civil & Mechanical Engineer · Building engineering calculators at calcengineer.com
Civil & Mechanical Engineer. Building free engineering calculators at calcengineer.com — HVAC, electrical, structural and more. 600+ calculators in progress.